BinaalineThe construction encyclopedia

Key points

  • A direct cooler passes air through wet pads 8 to 12 inches thick, dropping its temperature by about 15 to 40°F (roughly 8 to 22°C) while adding humidity.
  • Suited to climates with a 1% summer design wet-bulb temperature below 70°F (about 21°C); performance falls as humidity rises.
  • It can use about a quarter of the energy of central AC, but it uses water and needs relief openings: 2 ft² of free area per 1,000 CFM.
  • Empty the pan if the unit will sit idle for more than a few days; standing water breeds mosquitoes and bacteria.
Written for:Owner

Evaporative (desert) coolers are common in rest houses, workshops, warehouses and some homes. The idea is simple: evaporating water draws heat out of the air. But they are not a universal replacement for ordinary AC; success depends on dry air.

1) How it works

  • Direct: a housing with a large blower and sponge-like media 8 to 12 inches thick kept wet; air passes through, water evaporates, and the air temperature drops by 15 to 40°F (roughly 8 to 22°C)1, but the air entering the house becomes more humid.
  • Indirect: an air-to-air heat exchanger with two separate air paths, cooling supply air without adding humidity because the moist air is exhausted separately1.
  • Two-stage (indirect then direct): combines both, with an evaporative cooling efficiency of 95% or more according to the source1.

2) When it helps and when it doesn't

It suits areas where the 1% summer design wet-bulb temperature is below 70°F (about 21°C), and can work up to 74°F (about 23°C) with reduced performance1. The source contrasts a hot, dry city where it works well with a cooler but humid one where it does not1.

In plain terms: the drier the air, the more an evaporative cooler cools. On humid days or in humid places its cooling drops and the space feels damp. Your city's design wet-bulb temperature is in the climate design data your engineer or designer uses.

3) Compared with ordinary (compressor) AC

ItemEvaporative coolerCompressor AC
ElectricityCan use about a quarter of the energy of central AC1Higher; see the AC guide and efficiency label
CostCan cost less than half as much to install and run as central AC1Higher
WaterUses water; for a 1,500 ft² (about 140 m²) home, annual use in the source's examples ranged from 2,980 to 12,457 gallons depending on the city1Uses no water (it produces condensate)
HumidityDirect type adds indoor humidityRemoves humidity
WindowsNeeds relief openingsWorks with the space closed

4) Relief openings: a requirement, not an option

An evaporative cooler pushes outside air in, so it needs a way out. The source states: for every 1,000 CFM of air delivery, 2 ft² (about 0.19 m²) of unrestricted relief area is required1. Without it, pressure and humidity rise and cooling weakens.

5) Maintenance

  • Start of season: clean or replace the pads, check belt tension, and clean the cabinet1.
  • During the season: empty the pan if the unit will sit idle for more than a few days, because standing water breeds mosquitoes and bacteria1.
  • End of season: shut off the water line, drain and clean the pan, and cover the unit1.
  • Bleed-off valve: reduces mineral build-up but increases water use by 10% to 50%1.

Practical advice: hard, salty water speeds scale on the pads; watch them and replace them when they stiffen. Water and power connections for a roof unit must be rated for outdoor use; see outdoor electrics.

Sources

The number next to a statement points to its source in this list. Sources back the general information; anything marked “practical advice” is editorial experience, not a quoted source. Anything that affects safety, structural design or electrical installations needs a licensed professional, and in Saudi Arabia the binding reference is the Saudi Building Code.

  1. 1Evaporative Cooling Systems (Building America Solution Center) — Pacific Northwest National Laboratory / U.S. DOE
Was this guide useful?
This guide is for general information and planning, based on standards and technical guides. Standards are revised periodically; in Saudi Arabia the binding reference is the Saudi Building Code and the instructions of the competent authorities. For design and execution, use a licensed engineer or technician. Found an error? Tell us.