Key points

  • The International Building Code requires airborne sound insulation of at least STC 50 in the lab (45 if field tested) between dwelling units, and the same for impact sound (IIC) in floor-ceilings.
  • The Saudi General Building Code SBC 201 (2024 edition) includes a 'Sound Transmission' section (1206); confirm its adopted text with the engineering office.
  • Ratings belong to the complete assembly (a wall or floor with all its layers), not a single material; there is no such thing as 'total' soundproofing.
  • In NRC research a wall rated STC 52 in the lab gave only ASTC 44–45 between rooms because of sound travelling through the floor; fixing a building after construction costs far more than designing it right.
Written for:OwnerContractorSupplier

Noise from neighbours is one of the most common complaints in flats and apartment buildings. Many products sold as "sound insulation" do not address the real path the sound takes. This guide explains how sound travels, what the code requires, and what has been shown in tests to make a real difference.

1) Two kinds of sound

TypeExamplesLab ratingField rating
AirborneVoices, TV, musicSTC per ASTM E90NNIC per ASTM E336
Impact (structure-borne)Footsteps, dropped objects, moving chairsIIC per ASTM E492NISR per ASTM E1007

Source: the 2021 International Building Code12. The higher the number, the better the insulation.

2) What does the code require?

  • Airborne sound: walls, partitions and floor-ceilings separating dwelling units from each other or from public or service areas (such as corridors): STC of at least 50 in the lab, or NNIC of at least 45 if field tested1.
  • Impact sound: floor-ceilings between dwelling units: IIC of at least 50 in the lab, or NISR of at least 45 in the field2.
  • Penetrations: openings for pipes, electrical boxes, recessed cabinets, bathtubs and HVAC or exhaust ducts must be sealed, lined or insulated so the required rating is maintained1.
  • Entrance doors: exempt from the number, but must fit tightly to the frame and sill1.
In Saudi Arabia: Chapter 12 of the Saudi General Building Code SBC 201 (2024 edition) includes a section titled "Sound Transmission" (Section 1206)3, and the Saudi code is based on the International Building Code. The full text of the section is not published free of charge on the Saudi Building Code website, so ask the engineering office to confirm the adopted figures for your project.

3) Why does sound get through when the wall is good?

Sound does not only cross the separating wall; it shakes the floor, ceiling and adjoining walls, and the vibration travels through the junctions into the next room. This is flanking transmission, and the result the occupant actually hears is rated ASTC4.

In National Research Council Canada tests on wood-frame buildings4:

  • A wall rated STC 52 in the lab gave only ASTC 44–45 between the rooms, because the floor carried more sound than the wall itself.
  • Adding a layer of gypsum board raised the wall to STC 57, but the real result only reached ASTC 43, because the main path (the floor) was not treated.
  • Adding a topping over the floor raised the result to ASTC 50 (with a panel layer) and 56 (with gypsum concrete over a resilient mat).
  • Fixing flanking after construction is much more expensive than addressing it in the design.
In practice: do not spend on "strengthening the wall" before you know where the sound comes from: the floor? the ceiling? a pipe opening? the door? The figures above come from wood-frame buildings, and most Saudi buildings are concrete, but the principle is the same: performance belongs to the whole system, not the wall alone.

4) Block walls

From the National Research Council Canada guide on concrete block walls5:

  • Weight matters most: the higher the mass per square metre, the better. A single-leaf block wall gives about STC 45–55 when its surface is sealed with paint or plaster.
  • Porous (lightweight) block: sealing the surface with plaster or block sealer improves insulation significantly; gains of 5 to 10 STC points or more are not uncommon for some lightweight blocks.
  • Joints: mortar joints must be complete with no gaps; a gap in a joint leaks sound.
  • Gypsum board glued directly to the block does not seal it as well as plaster or paint.
  • Filling block cores with absorbent material does not help; sound passes through the block body. Filling with sand or grout only adds weight.
Wall thicknessLightweight blockNormal-weight block
90 mmSTC 43STC 44
140 mmSTC 44STC 46
190 mmSTC 46STC 48
240 mmSTC 47STC 49

Representative values for 50% solid blocks sealed on at least one side, from the same guide5. Note that thickness alone raises the figure only a little.

5) Adding gypsum board: how to make it work

The effective way to upgrade an existing block wall is to add gypsum board not rigidly connected to the block, with a cavity and absorbent material5:

  1. Support: best is independent studs that do not touch the block, or resilient metal channels. Rigid furring carries sound straight through.
  2. Cavity depth: the deeper the better. A shallow cavity can reduce insulation instead of improving it.
  3. Absorbent material in the cavity: fibres such as rock wool, glass fibre or cellulose. Closed-cell foam such as polystyrene does not absorb much sound.
The guide's rule: the mass of the gypsum board (kg/m²) multiplied by the cavity depth (mm) should exceed 425 for a cavity filled with absorbent material, and 720 for an empty cavity5.

In lightweight-wall research, mounting gypsum board on resilient channels increased the attenuation of a flanking path by at least 10 dB, while adding a second directly fixed layer added only 1 to 2 dB4.

6) Double walls: excellent on paper, sensitive in execution

Two separate leaves with a cavity can give very high insulation, but any bridge between them ruins it. In one test a double wall expected to exceed STC 70 gave only STC 60 because mortar droppings in the cavity connected the two leaves; such errors are hidden inside the wall and cannot be fixed after construction5.

Practical advice: ask the contractor to keep the cavity clean during construction, and photograph it before closing. See the handover checklist.

7) Footsteps from the flat above

  • The code requires IIC 50 for floor-ceilings between units2.
  • In NRC research, the most effective improvement between units one above the other was adding layers over the floor, best a heavy topping over a resilient mat; improving the ceiling alone without treating the walls gave limited benefit4.

Practical advice: carpet and resilient underlays reduce footstep noise. Tiles bonded directly to the concrete slab with no underlay transmit impact noise easily. In a new building this is decided at design stage, because a floating floor raises the floor level.

8) Pipes, AC units and doors

  • The code requires openings for pipes and HVAC or exhaust ducts through a separating wall or floor to be sealed, lined or insulated1.
  • The entrance door must fit tightly to the frame and sill1.

Practical advice (not regulatory text): support drain pipes with rubber-lined hangers, avoid running them inside a bedroom wall where possible, put the AC outdoor unit on anti-vibration mounts, and seal around back-to-back electrical boxes on either side of a separating wall.

9) New or existing building?

New building (at design stage)

  • A heavy or double separating wall with junction details.
  • A floating floor or resilient mat under the finish.
  • Pipe routes planned away from bedrooms.
  • Lower cost for the same result.

Existing building (retrofit)

  • Find the path first: wall, floor, ceiling, door, opening.
  • Sealing openings and tightening the door is often the cheapest step.
  • Gypsum board on resilient channels or independent studs with wool in the cavity.
  • More expensive, and the result is limited by flanking.

10) Before you buy "soundproofing"

  1. Ask for a test report for the complete assembly (the wall or floor with all its layers) to ASTM E90 or E492, not a figure for a single material.
  2. Note: foam and decorative absorbent panels reduce echo inside the room; they do not stop sound reaching the neighbours.
  3. There is no "total" soundproofing; any promise of complete silence is an exaggeration.
  4. For sensitive projects (plant rooms, studios, hotels) ask for an acoustic engineer and field measurement.

See also: gypsum board · blocks · insulation materials compared.

Sources

The number next to a statement points to its source in this list. Sources back the general information; anything marked “practical advice” is editorial experience, not a quoted source. Anything that affects safety, structural design or electrical installations needs a licensed professional, and in Saudi Arabia the binding reference is the Saudi Building Code.

  1. 12021 International Building Code, Section 1206.2 Airborne sound — International Code Council (ICC)
  2. 22021 International Building Code, Section 1206.3 Structure-borne sound — International Code Council (ICC)
  3. 3Saudi General Building Code SBC 201-CR-2024 — table of contents (Chapter 12, Section 1206 Sound Transmission) — Saudi Building Code National Committee
  4. 4Airborne Sound Insulation in Multi-Family Buildings, Construction Technology Update No. 66 (Quirt & Nightingale) — National Research Council Canada
  5. 5Controlling Sound Transmission through Concrete Block Walls, Construction Technology Update No. 13 (Warnock) — National Research Council Canada
Was this guide useful?
This guide is for general information and planning, based on standards and technical guides. Standards are revised periodically; in Saudi Arabia the binding reference is the Saudi Building Code and the instructions of the competent authorities. For design and execution, use a licensed engineer or technician. Found an error? Tell us.