Key points
- The earth wire connects the metal parts of appliances to earth, giving fault current a path so the protective device disconnects.
- In a TT system the fault current is usually too small to operate an ordinary breaker, so an RCD is essential there.
- In a TN system a fault becomes a large current that the breaker clears, and RCDs may also be needed.
- Do not measure or open the panel yourself; ask a licensed electrician for a documented test under the Saudi Electrical Code SBC 401.
"The washing machine gives a shock", "the iron tingles", "the breaker didn't trip": all things you hear when the protection system is incomplete. Protection at home has three parts that work together: the earth wire, the breaker, and the RCD.
The binding reference in Saudi Arabia is the Saudi Electrical Code SBC 4011. The examples in this guide come from international guides and only explain the principle; the values required for your building are set by the code and the designer.
1) Who does what?
| Part | Its job | What it does not do |
|---|---|---|
| Earth wire (PE) | Connects appliance metalwork to the earthing system, so if a live wire touches the casing the current has a path other than your body | It does not disconnect power on its own; it needs a protective device to trip |
| Breaker (MCB) | Trips on overload or short circuit (large current) | Does not sense small leakage that can still be dangerous to people |
| RCD | Senses the difference between outgoing and returning current and trips quickly | Does not protect against overload, and does not replace earthing |
For breakers and 30 mA sensitivity: breakers and RCDs.
Why neither replaces the other
- Fault protection needs both: the Schneider guide states that protection against an insulation fault is achieved by automatic disconnection of the supply if the exposed conductive parts of equipment are properly earthed, at two levels: earthing all exposed conductive parts with an equipotential bonding network, then automatic disconnection of the faulty section2.
- An RCD detects leakage whatever its path: it works by detecting residual currents to earth, which may or may not pass through a person, and disconnects fast enough to prevent injury3. In a TT system, automatic disconnection is achieved by an RCD, with all exposed conductive parts connected to a common earth electrode4.
- Why "additional protection": the guide calls a high-sensitivity RCD (30 mA or less) additional protection because the other preventive measures are not infallible: lack of maintenance, carelessness, worn insulation, accidental contact and immersion in water3.
2) TT and TN in brief
- TT: all metalwork in the building connects to the building's own earth electrode. The fault path runs through two earth electrodes, so the fault current is generally too small to operate breakers or fuses, and an RCD is essential in this system4.
- TN: metalwork connects directly to the earthed point of the supply through protective conductors, so any insulation fault becomes a phase-to-neutral short circuit with a large current the breaker clears; the guide notes RCDs may also be necessary5.
Which system your home has depends on the supplier and the electrical design; ask your electrician.
3) A worked example (from the Electrical Installation Guide)
In a TT example: supply earth electrode 10 Ω, building electrode 20 Ω, giving a fault current of only 7.7 A and a fault voltage on the casing of 154 V, which is dangerous. An ordinary 16 A breaker will not trip at that current, while a 300 mA RCD trips in about 30 ms4.
| RCD sensitivity | Maximum earth electrode resistance (50 V limit) |
|---|---|
| 300 mA | 166 Ω |
| 30 mA | 1666 Ω |
Source for the table and example: the Electrical Installation Guide4. The figures illustrate the principle only; the values required for your building are set by the code and the designer.
4) How to request a documented test
- Hire a licensed electrician or firm, and ask for a written report, not a verbal opinion.
- Ask that it includes: the earthing system type, the earth measurement result, continuity of protective conductors to sockets, and RCD trip-time tests.
- Ask for the panel circuits to be labelled and the RCD-protected circuits identified.
- Keep the report with the house documents. See new building handover.
5) When to call an electrician immediately
- A tingle when touching an appliance, tap or metal door.
- The RCD trips and will not reset, or does not trip when the test button is pressed.
- Sockets without an earth terminal in a kitchen, bathroom or laundry.
- A burning smell or heat at a socket or panel. See electrical problems.
The binding reference in Saudi Arabia is the Saudi Electrical Code SBC 401, as noted at the top of this guide.
Sources
The number next to a statement points to its source in this list. Sources back the general information; anything marked “practical advice” is editorial experience, not a quoted source. Anything that affects safety, structural design or electrical installations needs a licensed professional, and in Saudi Arabia the binding reference is the Saudi Building Code.
- 1Saudi Electrical Code SBC 401 — code requirements (based on IEC 60364 with local amendments) — Saudi Building Code National Committee
- 2Protection against indirect contact — Electrical Installation Guide — Schneider Electric — Electrical Installation Guide
- 3Additional protection: High sensitivity RCDs — Electrical Installation Guide (Schneider Electric)
- 4TT system - Principle — Electrical Installation Guide (Schneider Electric)
- 5TN system - Principle — Electrical Installation Guide (Schneider Electric)