Key points

  • EN 14891 classifies liquid-applied waterproofing under tiles as CM cementitious, DM dispersion, RM reaction resin.
  • All types must be watertight, achieve adhesion ≥ 0.5 N/mm² after water, heat and lime exposure, and bridge cracks ≥ 0.75 mm.
  • Class P: resistant to chlorinated water (pools). Class O: crack bridging at low temperature.
  • The waterproofing must be tested (flood test) before tiling.
Written for:OwnerContractor

One of the most common renovation problems: damp in the wall of the room next to the bathroom, or a leak into the ceiling below. The cause is often the false belief that tiles "waterproof". In fact cement grout absorbs water (at rates set by the standard)1, and water finds its way through joints and cracks. The solution is a waterproofing membrane under the tiles.

1) Types of liquid-applied membranes (EN 14891)

CodeTypeDescription
CMCementitiousHydraulic binders (cement) with aggregates and polymer additives, mixed with water or a special liquid before use1.
DMDispersionOrganic binders as an aqueous polymer dispersion with additives and fillers1.
RMReaction resinSynthetic resin with fillers that hardens by chemical reaction1.

2) Basic requirements for all types

TestRequirement
Initial tensile adhesion (after 28 days)≥ 0.5 N/mm²
Adhesion after water contact (21 days immersion)≥ 0.5 N/mm²
Adhesion after heat ageing (14 days at 70°C)≥ 0.5 N/mm²
Adhesion after freeze–thaw cycles (25 cycles)≥ 0.5 N/mm²
Adhesion after immersion in lime water (7 days)≥ 0.5 N/mm²
WatertightnessNo penetration allowed
Crack bridging under standard conditions≥ 0.75 mm

Source: technical bulletin TDS 137EN1.

3) Additional classes

  • P: adhesion ≥ 0.5 N/mm² after a 28-day cure including 7 days immersed in chlorinated water, i.e. resistance to contact with chlorinated water1.
  • O: crack bridging at low temperature (−5°C)1.

Example: CM OP = a cementitious liquid membrane that bridges cracks in the cold and resists chlorinated water.

4) Where must you waterproof?

  • The whole bathroom floor, turned up the walls (higher in the shower area).
  • Kitchen and laundry floors.
  • Tiled balconies and roofs.
  • Pools and water tanks (with class P).

Upstand heights on walls and corner details are set by the designer, the product data sheet and the adopted code.

5) Details that make the difference

These are accepted professional practices in under-tile waterproofing systems; the final reference is the installation data sheet of the product used:

  1. Corners: reinforced with a dedicated flexible tape where floor meets wall and between walls.
  2. Pipe outlets and drains: treated with dedicated collars from the same waterproofing system.
  3. Thickness and number of coats: per the data sheet; usually two coats applied crosswise.
  4. Flood test: after full drying, plug the drain and flood the surface for a period set by the supervisor, watching the ceiling below before tiling.
  5. Compatibility: use an adhesive compatible with the membrane (preferably from the same manufacturer).
For owners: ask the contractor for photos of the waterproofing before tiling, and attend the flood test. It's the cheapest step in a renovation and the most expensive mistake if skipped.

6) Layers and failure points by location

Shower floor layersFrom top to bottom: Slip-resistant floor tile with grout, then Flexible tile adhesive (e.g. C2), then Liquid membrane + corner tapes, up the wall, then Screed sloped towards the drain, then Concrete slabSlip-resistant floor tile with groutFlexible tile adhesive (e.g. C2)Liquid membrane + corner tapes, up the wallScreed sloped towards the drainConcrete slab
A simplified shower floor section from top to bottom. Membrane type, thickness and how it is clamped at the drain follow the manufacturer's system.

A simplified bottom-up layer order for a tiled bathroom or balcony floor (the actual system follows the design and product sheet):

LayerFunctionCommon failure point
5. Tiles and groutFinishTiles and grout are not waterproofing; water passes through them
4. AdhesiveBonds the tilesAdhesive not compatible with the membrane
3. Membrane (EN 14891)Stops water penetratingCorners, pipe outlets, the drain, and insufficient thickness
2. Screed to fallsDirects water to the drainA reverse fall that traps water
1. SlabStructural baseCracks that move more than the membrane can bridge
LocationWhat is specificDetails
Bathroom and showerMembrane turned up the walls, especially in the showerbathroom renovation
BalconySun and rain exposure; the door threshold is criticalexterior finishes
PoolA class P membrane resistant to chlorinated waterpools
RoofUsually roof membrane systems, not under-tile membranesroofs and slabs

There is no "leak-proof guarantee" just because there are tiles, grout or a single product; the complete system with its details and a flood test is what prevents leaks.

Sources

The number next to a statement points to its source in this list. Sources back the general information; anything marked “practical advice” is editorial experience, not a quoted source. Anything that affects safety, structural design or electrical installations needs a licensed professional, and in Saudi Arabia the binding reference is the Saudi Building Code.

  1. 1EN 12004 Classifications – TDS 137EN — LATICRETE International
Was this guide useful?
This guide is for general information and planning, based on standards and technical guides. Standards are revised periodically; in Saudi Arabia the binding reference is the Saudi Building Code and the instructions of the competent authorities. For design and execution, use a licensed engineer or technician. Found an error? Tell us.